■ 제품필수정보
제조사 |
Eaton |
제조사품명 |
239101 FAZ6-C10/2 |
간략설명 |
Eaton xEffect FAZ6 MCB, 2P Poles, 10A Curve C, 230 ??400V AC, 6 kA Breaking Capacity, MCB |
■ 제품사양
Number of Poles = 2P
Current 등급 = 10A Tripping Characteristics =
타입 C Rated AC Voltage = 230 ??400V Range = xEffect Breaking Capacity at Maximum Voltage Rating = 6 kA Circuit Breaker
타입 = MCB Mounting Style = DIN Rail Mount Width = 17.5mm Length = 80mm Depth = 62mm
타입 C MCB's. Professional range of FAZ6 series miniature circuit breakers (MCB ??s) from Eaton. These
타입 C circuit breakers are designed for use with residential applications. FAZ6 series MCB ??s are available with either 1, 2, 3 or 4 pole with an instantaneous release response current of 5-10In. All models are highly reliable and excellent quality. Features and Benefits. Thermal-magnetic overcurrent protection Power to the miniature circuit breakers can be fed from the line or load side Clear indication of contact position via front switch toggle Easy installation on DIN rail. MCB module width of only 17.5 mm (per pole) Six levels of short-circuit protection, categorized by
타입 B, C, D, K, S and Z curves Small modular width of the device and accessories saves space in the panel or equipment, which can lead to cost savings Available in single pole up to 4 pole Dual rating for IEC 60947-2 standard MCB Module widths: 1P 17.5mm, 2P 35mm and 3P 52.5mm. Standards. IEC 898; BS/EN60-898; EN50 022/DIN46277-3 (BS5584). FAZ-C*/* ; FAZ-S*/* = IEC/EN60947-2 IEC 60947-2 Relates to Low Voltage Circuit Breakers for use in industrial and similar installations. In the UK these are traditionally known as miniature circuit breakers (MCBs), moulded case circuit breakers (MCCBs) and also air circuit breakers (ACBs). What are the differences between the Tripping Curves?.
타입 B: Instantaneous trip when the electrical current through the device is 3 to 5 times the rated current. The type B trip curve MCBs are designed for standard circuit protection, typically protection of generators, persons and very long cables
타입 C: Instantaneous trip when the flow-through current is 5 to 10 times the rated current.
타입 C trip curve residential and domestic MCBs are used for higher inrush currents such as in machines and lighting, providing overload protection of circuits and other consumer units.
타입 D: Instantaneous trip when the flow-through current is 10 to 14 times the rated current. D curve MCBs are suitable for inductive and capacitive loads like transformers condensers. and electric motors.
타입 K: Instantaneous trip when the flow-through current is 10 to 14 times the rated current.
타입 K curve MCBs are suitable for inductive loads like transformers, condensers. and electric motors.
타입 S: Instantaneous trip when the flow-through current is 13 to 17 times the rated current. Suitable for applications where high levels of inrush current are expected. The high magnetic trip point of type S curve MCBs prevents nuisance tripping in high inductive applications such as motors, transformers and power supplies.
타입 Z: Instantaneous trip when the flow-through current is 2 to 3 times the rated current. Z curve MCBs are intended for use in electrical circuits that require a very low short circuit trip setting, for example, semiconductors.