■ 제품필수정보
제조사 |
Sick |
제조사품명 |
PAC50-BCC |
간략설명 |
Sick Pressure Switch, 4 mm Pneumatic Hose, G 1/4 Female, M12 5-Pin -1bar to 1 bar |
■ 제품사양
Minimum Operating Pressure = -1bar Maximum Operating Pressure = 1 bar Pressure
타입 = Negative Pressure, Positive Pressure Suitable Media = Air Connection = 4 mm Pneumatic Hose, G 1/4 Female, M12 5-Pin Voltage Rating = 17 ??30V dc Connection Thread Size = 1/4 in, M12 Manufacturer
시리즈 = PAC50 Contact Operation = Normally Closed, Normally Open Connection Thread Standard = G, Metric
최소 작동 온도 = 0°C
최대 작동 온도 = +60°C IP Rating = IP65, IP67 Output Range = 0 to 10 V, 4 to 20 mA PAC50 Pressure Switches. The SICK PAC50 pressure switch provides an easy to read overview of important system information using a clear bi colour display. Simple to programme making commissioning fast and easy, the PAC50 provides up to 2 switch outputs and an extra analogue output in a rugged casing. Switched outputs can be programmed to be NPN, PNP or push-pull. Analogue inputs automatically detect whether a voltage or current signal is required simplifying installation and reducing stocking cost. Features and Benefits. Integrated pressure switch, transmitter and display Clear simultaneous display of applied pressure and set points
색상 change when set points are reached 3 large push buttons DIN rail or panel mounting (via accessory) Standard M12 electrical connection PIF connection or 2 x G1/4 female (1 on rear, 1 on bottom) Switch outputs configurable PNP, NPN, Push-pull. IO Link V1.1. Analogue outputs configurable 4-20mA / 0-10V Pressure ranges available -1 to 0 Bar, -1 to +1 Bar, 0 to 6 Bar, 0-10 Bar. Set-up and Installation. Installation and set-up of the PAC50 is fast and easy with no tools required for programming. Mounting is done using the integrated DIN Rail Mounting on the back or with the panel and wall mounting kit available separately (1000682). Set-up and commissioning are done by using the three buttons on the front panel. Use the arrow keys to navigate the menu and the middle key to select the required parameter. Then simply use the arrow keys and adjust to the required set point before saving by using the middle key. Your PAC50 is now ready for operation. Applications. The PAC50 is suitable for use with both positive pressure and vacuum systems in a range of applications including pneumatic control systems, vacuum grippers and cylinder pressure regulation.